All generator sizes on this site use one shared load sheet: the running load comes from the optional dwelling calculation in NEC 220.83, followed by the largest motor start and the fuel derate. For your permit, the electrician's own load calculation is what governs.

The load sheet, shown line by line

Worked through: a 2,000 sq ft home heated by gas with a 3-ton central air conditioner.

LineRule2,000 sq ft example
General lighting and outlets3 VA per sq ft6,000 VA
Small appliance circuits2 kitchen circuits at 1,500 VA3,000 VA
Laundry circuit1 circuit1,500 VA
Fixed appliancesnameplate watts of each one you picknone picked
Subtotal of the lines aboveadded10,500 VA
Counted: the first 8,000 VA of the subtotalat 100%8,000 VA
Counted: the rest of the subtotalat 40%1,000 VA
Counted: heating or cooling, whichever is largerat 100%4,300 VA
Running loadthe counted lines added together, with 1,000 VA read as 1 kW13.3 kW

Citing NEC 220.83 by section, this page doesn't reproduce the code text, which is NFPA's.

Starting watt figures

For one or two seconds while starting, a motor pulls two to three times the watts it runs at. The largest motor start is added to the running load on the sheet, because motors seldom start together. For the example, the central ac, 3 ton, contributes 2.5 kW, giving a peak of 15.8 kW. With a soft starter on the air conditioner, about 35% of that surge remains.

The running load must be no more than 80% of the generator's rating, while the peak must be carried at full rating. Whichever of these two needs more power sets the size.

Derate

Natural gas output is lower for a standby generator than propane output. The sheet applies 89% of the propane rating, based on the manufacturers' spec sheets. Once you're above 500 ft, every extra 1,000 ft costs the engine about 3.5% of its power. That example calls for 18.7 kW, so a generator of 22 kW comes next.

Gasoline is what portables are rated for, and unless the manufacturer lists a portable's starting watts, the sheet counts them at 125% of its running rating.

Cost figures and sources

FigureSourcePeriod
Appliance running and starting wattsWattage chart from Champion Power Equipment; EV charger running on 32 A and 240 Vas published
Fuel per hour by sizeGenerac spec sheets, half and full loadas published
Natural gas costs $21.92 per thousand cubic feet on average in the USEIA residential natural gas prices by stateMarch to August 2026
Propane, $2.73 a gallon, US averageEIA heating oil and propane updateOctober 26, 2026
Gasoline, $4.27 a gallonEIA gasoline and diesel updateOctober 26, 2026
Electrician wage, $34.37 an hour, US averageBLS Occupational Employment and Wage StatisticsMay 2025
Outage minutes a year by stateEIA Electric Power Annual, table 11.4 (SAIDI)2025
Generator list pricesGenerac and Kohler price pagesread 2026-11-01
Install labor, $3,000 to $5,500Install ranges published by Home Depot, Angi and PowerOutage.usas published
Sound levelsManufacturers' spec sheetsas published

Each figure is an estimate used for planning. Your site, gas run and electrician all affect the cost.